County of Maui Water Supply

Sec. 2-4

Fire Protection

  (a)    All subdivisions in business, industrial, hotel, commercial, duplex,
      apartment, airport, rural, and residential districts shall be required
      to install fire hydrants which shall be paid for by the subdivider and
      shall be in accordance with these regulations.  Subdivisions in
      agricultural districts shall be required to install standpipes.
      Subdivider may elect to instal] fire hydrant in lieu of standpipe in
      agricultural districts.
  (b)    Fire hydrants shall be spaced along the streets not more than 250
      feet apart in business, commercial, industrial, hotel, and apartment
      districts, not more than 350 feet apart in residential districts, and
      not more than 500 feet apart in rural and agricultural districts.
         Standpipes shall be spaced not more than 500 feet apart.  The
      department shall determine the location of all hydrants and standpipes.
      All standpipes and fire hydrants required for adequate fire protection
      of a subdivision shall normally be located within the subdivision.
         If, in the interest of better fire protection, it is determined
      that one or more of the required hydrants may serve the subdivision to
      better advantage if located outside the subdivision, they may be so
      located with cost to be borne by the subdivider.
  (c)    In fixing the standards for fire protection insofar as water supply
      is concerned, the department shall be guided by the standards of the
      Insurance Services Office's Guide for Determination of Required Fire
      Flows.  The minimum fire protection schedule shall be as follows:

                          FIRE PROTECTION SCHEDULE

                       MINIMUM FIRE FLOW REQUIREMENTS
                             BY ZONING DISTRICT
           DISTRICT                  G.P.M.                  HOURS
           Agricultural                250                      2
           Rural                       400                      2
           Residential               1,000                      2
           Duplex                    1,250                      2
           A-1 Apartment             1,500                      2
           A-2 Apartment             2,000                      2
           Hotel                     2,500                      2
           Business                  2,000                      2
           Light Industrial          2,000                      2
           Heavy Industrial          2,500                      2

  (d)    Fire hydrants and standpipes are not required for new subdivisions
      which fall completely within a radius of (l) 250 feet from the nearest
      existing fire hydrant in business, industrial, commercial, hotel, and
      apartment districts, (2) 350 feet from the nearest existing fire
      hydrant in residential districts, and (3) 500 feet from the nearest
      existing fire hydrant or standpipe in rural and agricultural districts.
      Where subdivisions or any portion of the new subdivision is outside
      such radius, compliance with subsections (a) and (b) shall be required.

"By Water All Things Find Life"

Department of Water Supply
County of Maui
200 South High Street
Wailuku, HI 96793-2155
Telephone (808) 270-7816
Fax (808) 270-7951

[Back]